Solution for sf6 gas reclaimer cart

SF6 HANDLING PROCEDURE - US EPA halogen leak detector. Test the gas for arc byproducts if there is a possibility of an internal failure. 2) Identify any components that must be repaired while SF6 gas is evacuated from equipment. 3) Obtain replacement parts as necessary to repair leaks. 4) Attach the hose from the SF6 Processing Cart to the gas compartment valve. 5) Draw a vacuum on the hose to remove air and moisture.